For Licensed Electrical Contractor, UL-508A Panel Shop & Electrical PE Review • NEC Articles 250, 430, 445, 551 & UL-508A Reference
Allows operation from a standard restaurant 240V 50A twist-lock shore receptacle OR the onboard 20 kW diesel generator without 3-phase utility service.
| Ckt # | Breaker | Equipment Tag & Description | HP / Watts | 240V 1Φ Input FLA | Wire & Conduit | Starter / VFD Type & Notes |
|---|---|---|---|---|---|---|
| MB-1 | 100A / 2P | Main Panel Disconnect (Fed from ATS-801 Load Terminals) | 24.0 kVA Max | 34.4A Avg / 54.6A Peak | 3#3 + #6 GND (1-1/4" EMT) | 22 kAIC thermal-magnetic + Type 1 SPD (50 kA) |
| CB-1 (1,3) | 30A / 2P | P-101 Raw Water Intake Pump (Stage 2) |
3.0 HP (2.2 kW) | 16.6A (1Φ In) → 9.6A (3Φ Out) | 2#10 + #10G (3/4" LFMC) | VFD-101: 5 HP 240V 1Φ-in / 230V 3Φ-out (derated 50%) + 3% reactor |
| CB-2 (2,4) | 20A / 2P | P-401 Contact Tank Transfer Pump (Stage 5) |
1.5 HP (1.1 kW) | 9.0A (1Φ In) → 5.2A (3Φ Out) | 2#12 + #12G (3/4" LFMC) | VFD-401: 2 HP 240V 1Φ-in / 230V 3Φ-out + 3% line reactor |
| CB-3 (5,7) | 30A / 2P | P-601A Kitchen Booster Pump Lead (Stage 6) |
3.0 HP (2.2 kW) | 16.6A (1Φ In) → 9.6A (3Φ Out) | 2#10 + #10G (3/4" LFMC) | VFD-601A: 5 HP 240V 1Φ-in / 230V 3Φ-out; PID on PT-603 |
| CB-4 (6,8) | 30A / 2P | P-601B Kitchen Booster Lag & UF Backwash Supply |
3.0 HP (2.2 kW) | 16.6A (1Φ In) → 9.6A (3Φ Out) | 2#10 + #10G (3/4" LFMC) | VFD-601B: 5 HP 240V 1Φ-in / 230V 3Φ-out; Lag booster + 40s UF BW |
| CB-5 (9,11) | 20A / 2P | CMP-801A/B Duplex Oil-Less Air Compressors |
2 × 1.5 HP | 6.8A (Lead) / 13.6A (Both) | 2#12 + #12G (3/4" EMT) | Duplex magnetic starter w/ alternator; lag starts if air < 65 PSI |
| CB-6 (10,12) | 20A / 2P | HVAC-901 Roof Heat Pump & Enclosure Freeze Heater |
2.4–3.1 kW | 10.0A – 12.9A @ 240V | 2#12 + #12G (3/4" EMT) | Wired through load-shed contactor CR-SHED (pauses during 50A Shore BW) |
| CB-7 (13) | 15A / 1P | UV-401A Amalgam UV Reactor Ballast (Duty — L1) |
450 W (120V) | 3.8A @ 120V (L1-N) | 2#12 + #12G (1/2" EMT) | Dedicated surge-filtered ballast circuit; 4–20mA UV intensity to PLC |
| CB-8 (14) | 15A / 1P | UV-401B Amalgam UV Reactor Ballast (Standby — L2) |
450 W (120V) | 3.8A @ 120V (L2-N) | 2#12 + #12G (1/2" EMT) | On opposite phase leg (L2) for redundancy; auto-start on UV-A fault |
| CB-9 (15) | 15A / 1P | CP-701 Dual 24VDC Power Supplies, PLC, HMI & Analyzers |
380 W (120V) | 3.2A @ 120V (L1-N) | 2#12 + #12G (Internal) | Redundant 24VDC 10A PSUs (diode auctioneered) + 30-min 24VDC UPS battery |
| CB-10 (16) | 15A / 1P | P-501/502A,B/503 Chemical Metering Pumps & STR-101 Motor |
320 W (120V) | 2.7A @ 120V (L2-N) | 2#12 + #12G (1/2" EMT) | 24VDC relay enable from PLC + 4–20mA speed pacing signal |
| CB-11 (17) | 15A / 1P | EF-901 Chemical Exhaust Fan (150 CFM) & Interior/Scene LEDs |
260 W (120V) | 2.2A @ 120V (L1-N) | 2#12 + #12G (1/2" EMT) | Exhaust fan runs continuously; forced high-speed on AIT-901 Cl₂ alarm |
| CB-12 (18) | 20A / 1P GFCI | Wet Lab Bench GFCI Receptacles & Exterior Service Outlet | 180 W Nom | 1.5A @ 120V (L2-N) | 2#12 + #12G (1/2" EMT) | Class A (5mA) GFCI breaker per NEC 210.8(B) for wet lab sink proximity |